UL FSRI full-scale experiments · April 2019 · Fixed ventilation and fire damage patterns

Ventilation and fire damage patterns — 3D reconstruction preview

UL FSRI ran 21 full-scale fire experiments, 13 in a single-story ranch and eight in a two-story colonial, at UL’s Large Fire Laboratory in Northbrook, IL, to examine how ventilation changes fire damage and fire patterns. These pages follow four of the ranch’s living room fires: experiments 1 and 2 with all exterior vents closed, experiments 3 and 4 with the front door open.

Interactive 3D · PDF annex (2.5 MB) · Video (2 min 20)

Key details from the source record

Study
D. Madrzykowski and C. Weinschenk, Impact of Fixed Ventilation on Fire Damage Patterns in Full-Scale Structures, UL Firefighter Safety Research Institute, April 2019
Objective
“To examine how differences in ventilation to full-scale structure fires result in changes to the fire damage and fire patterns within the structure” (p. 11)
These pages
Experiments 1 to 4, the ranch living room fires: section 4.1, pp. 49–81; discussion, sections 6.1.1 and 6.2.1
Independence
An independent illustration of the published study, not produced, reviewed or endorsed by UL FSRI
Credits
Lamp models by Kenney (CC0) · Three.js r128, MIT License · Illustrative models; not a laser scan, a fire simulation or a new finding

Step-by-step reconstruction sequence

Four separate fire experiments, two ventilation conditions, as the UL FSRI study reported them

  1. Step 01

    A ranch house built for fire tests

    Fig. 3.1, p. 14 · Fig. 3.2 and Table 3.3, p. 15 · leakage: 4 ACPH at 50 Pa, 0.08 m² at 10 Pa (p. 15)

    The single-story ranch had overall interior dimensions of 13.92 m by 7.7 m and 2.44 m ceilings: three bedrooms, a living room, a dining room and a kitchen, with walled-off areas protecting the instrumentation (pp. 12–13). To control ventilation repeatably, the windows were built as side-hinged wooden shutters (p. 14). A leakage test with all exterior vents closed placed the structure between a tight and a moderately tight house (p. 15).

    Stated by the report: the interior envelope, the ceiling height, the door and window openings and the furniture sizes of Table 3.7. Estimated: wall thickness and junctions, interior door positions, shutter framing, colours. The ceiling and the near walls are removed for viewing only.

  2. Step 02

    The living room fuel, and where the fire started

    Table 3.7, p. 33 · p. 37 · Fig. 3.18, p. 38 · section 4.1, p. 49

    The living room held two sofas, two upholstered chairs, two end tables with lamps, a floor lamp, a coffee table and a TV stand with a TV (p. 37, Table 3.7). In each experiment the first item ignited was the sofa against the wall to the right of the hallway, at “the left side of the sofa, at the intersection of the seat cushion, the arm rest, and the back cushion”, with a remote operated electric match (p. 49).

    Positions are estimated from Fig. 3.18. The TV keeps Table 3.7’s printed size (89.5 × 55.9 × 23 cm), an unusually short body; the carpet keeps the table’s 556 × 396 cm and is not a room boundary. The bedrooms were furnished too (p. 37) but are empty in the model: an omission, not evidence.

  3. Step 03

    Two front-door conditions, four separate experiments

    Table 3.1, p. 13 · Table 4.1 and p. 48 · p. 49

    Experiments 1 and 2 had all exterior doors and windows closed for their duration; experiments 3 and 4 had the front door open and every other exterior vent closed for the duration (p. 48). “The ventilation conditions were established prior to ignition and maintained throughout the experiment” (p. 49). In all four, bedroom 2 was open and bedrooms 1 and 3 closed (pp. 37, 50).

    The same front wall twice, side by side for comparison: each experiment kept its configuration, and no page shows the door opening or closing. The open door’s angle is illustrative.

  4. Step 04

    Experiment 1, door closed: from ignition to flashover

    Experiment 1 · Table 4.2, p. 51 · pp. 49–50

    Table 4.2: at 40 s flames extended past the top of the back of the sofa; at 80 s the hot gas layer (HGL) was at least 0.4 m below the ceiling; at 120 s flames reached the ceiling, the HGL was approximately 0.61 m thick and light gray smoke left around the top edges of the front door; at 150 s the HGL was approximately 1.2 m below the ceiling; at 180 s the room was transitioning to flashover.

    Flames, smoke and the layer are illustrative and appear only where Table 4.2 records them; they show no size, temperature or flow field. The layer is drawn flat over the living room; at 180 s the report puts it about 1.2 m above the floor between the ignition area and the front door.

  5. Step 05

    Experiment 1, door closed: the fire runs out of oxygen

    Experiment 1 · Table 4.2 and Fig. 4.1, p. 51 · p. 285

    At 185 s the carpet between the ignition sofa and the chairs ignited. At 190 s the living room shutters were pushed outward, with flames out of their top and bottom gaps until 205 s; at 200 s the HGL reached the floor. At 300 s: “Fire appears to have self-extinguished.” Post-test, the shutters were opened at 900 s and the front door at 962 s, with no active burning (Table 4.2).

    Fig. 4.1: just after 180 s living room temperatures rose above 800 °C, began to fall within 30 s and a minute later had dropped by more than 500 °C (p. 51). The door stays closed here; its opening at 962 s came after the fire.

  6. Step 06

    Experiment 3, door open: the same start, smoke leaves by the door

    Experiment 3 · Table 4.4, p. 65 · p. 64

    Table 4.4: at 40 s flames extended past the top of the back of the sofa, as in experiment 1; at 90 s smoke flowed out the open front door; at 135 s flames reached the ceiling and the HGL was approximately 0.9 m below it; at 180 s smoke flowed out the upper quarter of the doorway; at 210 s flashover began, flames reached the doorway and smoke filled its upper half.

    While the fire grew, the doorway was a unidirectional exhaust vent (p. 69), and pressures stayed below 20 Pa “because of the open front door” (p. 71). Table 4.4 gives one layer height, at 135 s, so the layer is drawn only then. Effects are illustrative.

  7. Step 07

    Experiment 3, door open: the fire keeps burning at the doorway

    Experiment 3 · Table 4.4, p. 65 · pp. 66, 69 · pp. 285, 288

    After flashover the flames at the door turned sooty and dark (255 s), clean (350 s) and sooty again (420 s), and the doorway “returned to being a bi-directional vent”: flames and smoke out of its upper half, fresh air in through the lower half (p. 66). At 300 s the fire was only burning near the open door (p. 288); the combustion zone later moved back toward the area of origin (p. 285).

    The report says experiment 3 burned for 6 min post-flashover (p. 64), and experiments 3 and 4 for approximately 7 min (pp. 259, 285). Flames, smoke and arrows are illustrative.

  8. Step 08

    Closed and open, side by side

    Section 6.2.1, pp. 285–289 · Figs 6.57–6.64

    With all vents closed, the living room fires “were ignited, flashed over, and self extinguished in less than 5 min”, burning 30 s or less post-flashover. With the front door open, they burned approximately 7 min post-flashover, until a hose stream about 10 min after ignition (p. 285). At 300 s the closed fires had self-extinguished; the open-door fires burned only near the door (p. 288).

    Fire damage is not modelled. The report shows it in photographs: Figs 6.57 and 6.58 (p. 286), the area of origin; Figs 6.59 and 6.60 (p. 287), the wall next to the front door, where the TV stand burned in the open-door experiments.

  9. Step 09

    What the study concluded

    Summary, pp. 341–342 · section 6.1.1, pp. 251–261

    From all 21 experiments the study draws four findings (p. 342). Its living room replicates were similar: with the door open, “both rooms were consistent with post-flashover burning and had similar, not identical, but similar damage patterns” (p. 261); with all vents closed, the time to flashover was slower in experiment 2 (p. 252).

    The findings are the study’s, quoted from p. 342; these pages add none. The rings mark locations only.

  10. Step 10

    Summary and sources

    These pages show the geometry and the two ventilation configurations of four separate UL FSRI experiments, each time and observation taken from that experiment’s own table or page. Fire damage and the other rooms’ contents are not modelled, the effects are illustrative, and nothing here is a simulation. The study’s photographs, videos and data are published at the addresses below.

    An independent illustration of the published study, not produced, reviewed or endorsed by UL FSRI. The report is © Underwriters Laboratories Inc.; its figures and photographs are cited, not reproduced.

Source & limitations: Shapes, positions and dimensions in the reconstruction are indicative; the report prevails.

Sizes follow the report where it states them; furniture placement, colours and the fire and smoke effects are illustrative. The report’s photographs and figures are cited by number and page, not reproduced.

Related service

3D reconstruction for property, fire and building claims

Need a confidential 3D reconstruction, QR-linked PDF annex, and video summary built from your own survey, engineering, or claim file?

See how we build property cases →

More public 3D case studies