Walker Consultants leak investigation report · July 28, 2023 · Northeast Stockton Library & Community Center

Stockton Library leak investigation — 3D reconstruction preview

Walker Consultants investigated reported leaks at the Northeast Stockton Library & Community Center, a one-story building under construction in Stockton, California, for the City’s Public Works Department. The City reported water intrusion and evidence of organic growth in the south-east section, and told Walker the project was on hold.

Interactive 3D · PDF annex (2.6 MB) · Video (1 min 46)

Key details from the source record

Report
Waterproofing Leak Investigation Report · Walker Consultants · July 28, 2023
Area
South-east section (Area A), along the east, south and west walls (p. 1)
Source
City of Stockton public exhibit, pp. 114–159
Credits
Illustrative 3D models based on Walker Consultants’ July 28, 2023 Stockton library leak investigation. Geometry and concealed details are approximate; not a survey or fluid simulation. · Three.js r128, MIT License

Step-by-step reconstruction sequence

The leak investigation step by step, as the consultant reported it

  1. Step 01

    Three specimens, one garden hose

    May 5, 2023 visual · May 22 water testing · June 19 walk with the manufacturers · pp. 1–2

    Walker visited on May 5, 2023 (no water was provided, so visual only) and returned on May 22 to test with water, with exploratory openings in the drywall at the south curtain walls. Water came from a garden hose, by controlled flow, and was turned off once intrusion was noted. Curtain walls not completely sealed could not be tested.

    The two models stand apart for reading: specimen 3 is a separate local corner, not placed relative to specimen 2. The text refers to a Figure 1 for the specimens, but no such figure is in the exhibit; photographs #2, #5 and #6 show the test locations.

  2. Step 02

    The wall around the window, layer by layer

    Layers illustrative · exploded spacing diagrammatic

    Specimen 2 taken apart, outside to inside: rainscreen cladding, membrane, sheathing, steel framing and gypsum board, with a sill pan under the window. Below the window the gypsum board is absent and the framing exposed, as photographed (photograph #9).

    Illustrative layers, thicknesses exaggerated. Frame depth and sightline are representative catalogue sizes; the installed system’s series is not identified. The sill pan’s shape is illustrative.

  3. Step 03

    Test 11: water along the sill, no leak observed

    Specimen 2 · test 11 · Table 1, p. 4

    On specimen 2 Walker sprayed water along the length of the sill. Table 1 records no leak observed. The other specimen 2 tests listed as “No”: 10, bottom corners of the two jambs; 14, their top corners; 15, along the head; 16, between the head and the flashing; 17, the rainscreen panels nearby.

    Table 1 lists specimen 2’s tests as 10, 11, 12, 14, 15, 16 and 17: test 10 also appears under specimen 1, and there is no test 13. The numbers are kept as printed.

  4. Step 04

    Test 12: above the operable sash, water comes in

    Specimen 2 · test 12 · photographs #9, #16, #17 · Table 1, p. 4

    With the sash closed, Walker sprayed above the operable sash of specimen 2, seen here from inside. Table 1: “Water leaked through the top of the casement for the operable sash, the unsealed holes in the perimeter of the frame and from the bottom of the casement.”

    Teal marks the three places Table 1 names, at approximate positions; amber, outside, where the hose was aimed. The concealed path of the water is not shown: the report does not trace it.

  5. Step 05

    Holes with no fastener and no sealant

    Report p. 6, item 1 · photographs #20, #21, #22

    The holes in the perimeter vents at the operable sashes were missing fasteners and sealant. Walker: “These holes act as a path for the water to enter the frame and potentially the interior of the building. The manufacturer’s details and shop drawings indicate that the holes should have a fastener and a sealant over them.”

    A generic profile enlarged 8×: the bore, the profile and the hole’s position are illustrative, not measured from the building.

  6. Step 06

    Gaskets and perimeter seals missing

    Report p. 6, item 1 · photographs #10, #23 to #26

    Weather gaskets the shop drawings show at the casement were missing: sealant was noted at some locations, and most locations were missing gaskets and sealants. Shims between the frame and the operable sash were visible, with no sealant joint. Walker also found vents not plumb, slide blocks missing and shipping snubbers left in place.

    The gap’s length and position are illustrative. The model does not show the shims, slide blocks or snubbers.

  7. Step 07

    Test 18, east elevation: water leaks in immediately

    Specimen 3 · test 18 · Table 1, p. 4 · report p. 6, items 2 and 4 · photographs #18, #19

    On specimen 3, on the east elevation, exterior sealant was incomplete at the bottom of the right-side jamb. Walker sprayed water there to confirm water intrusion: “Water leaked immediately into the interior.” Table 1 adds: “Mold was reportedly noted at this location and was remediated.”

    A separate local corner, not placed relative to specimen 2. The backer rod’s arrangement is representative. The concealed path of the water is not shown.

  8. Step 08

    The manufacturer’s walk: the installation is not complete

    Field observation report of June 22, 2023, reviewed on p. 5 · p. 6, item 3 · photograph #25

    On June 19, 2023 Walker walked the site with the curtain wall manufacturer. Its field observation report of June 22 notes the installation incomplete at the time of testing; pressure bar fasteners not torqued to the recommended pressure, covers not installed; daylight through the system; fasteners missing, openings unsealed; sash perimeter sealant missing; slide blocks missing; vents not plumb.

    The model has no pressure bar, fasteners or covers: the mark points at the frame member only. Interior perimeter sealant was also missing (p. 5).

  9. Step 09

    Recommended: complete the installation, then test again

    Preliminary recommendation 1 · p. 9 · flashing: p. 7

    Walker’s preliminary recommendation: correct and complete the curtain wall installation, including perimeter sealant, to the manufacturer’s requirements and the design documents; the contractor to perform QA/QC; then retest, with the architect, the manufacturer and the contractor on site. Further investigation of the flashing will depend on Walker’s observations.

    A conceptual comparison, not a repair: the report records no completed work and no retest. No flashing mechanism is shown.

  10. Step 10

    Summary: an incomplete installation, in the consultant’s preliminary reading

    “It appears to us that the leaks were caused due incomplete and incorrect installation” (p. 6): the consultant’s reading, with recommendations it calls preliminary. The general contractor had reported the glazing complete on May 5, and the curtain wall installation complete in an e-mail of June 2, 2023. The report contains no retest.

    Illustrative 3D models based on Walker Consultants’ July 28, 2023 Stockton library leak investigation. Geometry and concealed details are approximate; not a survey or fluid simulation. Three.js r128, MIT License. Source: City of Stockton public exhibit, pp. 114–159.

Source & limitations: Shapes, positions and dimensions in the reconstruction are indicative; the report prevails.

Illustrative component models, not the building: absolute scale is unknown and nothing is drawn to a measured size. Parties appear by role only. Photographs: Walker Consultants, Appendix A.